| Price | USD$180 |
| MOQ | 1 |
| Delivery Time | 8-16weeks |
| Place of Origin | china |
| Certification | CE |
| Model Number | KFD0-TT-Ex1 |
| Packaging Details | carton |
| Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
| Supply Ability | 500pcs |
| Connection side | field side | Signal type | Analog input |
| Place of Origin | china | Packaging Details | carton |
| Model Number | KFD0-TT-Ex1 | Supply Ability | 500pcs |
| Certification | CE | Brand Name | |
| Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram | Price | USD$180 |
| Delivery Time | 8-16weeks | Rated voltage | 12 ... 35 V DC loop powered |
| Minimum Order Quantity | 1 | Power dissipation | 0.4 W |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Rated voltage | 12 ... 35 V DC loop powered | |
| Power dissipation | 0.4 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1+, 2-, 3- thermocouple E, J, K, N, R, S or T, cold junction referenced to 0 °C (32 °F) | |
| Lead resistance | max. 100 Ω per line | |
| Current | lead monitoring ON: ≤ 15 nA; OFF: ≤ 1 nA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 9+, 8- | |
| Load | (U -12 V) / 0.02 A | |
| Current output | 4 ... 20 mA , limited to ≤ 35 mA | |
| Fault signal | downscaling ≤ 3 mA , upscaling ≥ 22 mA | |
| Transfer characteristics | ||
| Measuring range | span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable | |
| Deviation | ||
| After calibration | 0.1 % of full-scale value ± 1 K for the cold junction | |
| Temperature effect | temperature deviation 0.015 % of the span/K or 1.5 µV/K cold junction ± 2 K (calibrated at Tamb = 20 °C (68 °F)) | |
| Influence of supply voltage | 6.5 ppm/V | |
| Characteristic curve | the output voltage is linearly proportionate to the input voltage (not to temperature) | |
| Rise time | 250 ms | |
| Galvanic isolation | ||
| Input/Output | safe isolation according to EN 50178, rated insulation voltage 253 Veff | |
| Indicators/settings | ||
| Control elements |
DIP
switch rotary switch |
|
| Configuration |
via
DIP
switches via rotary switch |
|
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Insulation coordination | EN 50178 | |
| Galvanic isolation | EN 50178 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
|---|---|---|
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
| Height | 119 mm | |
| Width | 20 mm | |
| Depth | 115 mm | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-type examination certificate | ZELM 00 ATEX 0035 | |
| Marking |
II
(1)GD
[EEx
ia]
IIC
|
|
| Voltage | 16.1 V | |
| Current | 0.8 mA | |
| Power | 3.2 mW | |
| Output | ||
| Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) | |
| Certificate | TÜV 01 ATEX 1777 X | |
| Marking |
II
3G
Ex
nA
II
T4
|
|
| Galvanic isolation | ||
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |