40MVA Substation Power Transformer
This conservator-type substation power transformer is rated 40 MVA with a primary voltage of 44 kV and secondary voltage of 34.5 kV. It complies with ANSI/IEEE, CSA, DOE 2016 and multiple industry standards, and is designed for superior reliability and efficiency in the most demanding North American industrial and utility applications.
Product Photos
Technical Specifications
| Parameter |
Specification |
| Transformer Type |
Substation Power Transformer, Conservator Type |
| Phase |
Three Phase |
| Capacity |
40 MVA (40,000 KVA) |
| Vector Group |
Dyn1 |
| Primary Voltage |
44000V |
| Primary BIL |
250 KV |
| Secondary Voltage |
34500Y/19920 (26.4 to 34.5 kV (L-L) Range) |
| Frequency |
60 Hz |
| Temperature Rise |
65°C |
| Insulation Rating |
Class A Insulation |
| Cooling Class |
ONAN |
| Efficiency Standard(s) |
Meets ANSI/IEEE Standards |
| Fill Valve Location |
Top Mounted |
| Winding Material |
Copper |
| Ambient Temperature Rating |
40°C |
| Ambient Operating Temperature Range |
-40°C to +40°C |
Technical Drawings
Compliance and Standards
- Meets/Exceeds DOE 2016 Efficiency Ratings
- Meets/Exceeds CSA Efficiency Ratings
- Complies with ANSI / IEEE C57.12.00
- Complies with ANSI / IEEE C57 12.28
- Complies with ANSI / IEEE C57 12.29
- Complies with ANSI / IEEE C57 12.34
- Complies with ANSI / IEEE C57 12.35
- Complies with ANSI / IEEE C57.12.70
- Complies with ANSI / IEEE C57.12.110
- Complies with ANSI / IEEE C57.12.131
- Complies with ANSI / IEEE C62.11
- Complies with ANSI / IEEE C62.22
- Complies with ANSI / IEEE 386
- Complies with ANSI / IEEE C2
- Complies with ANSI / IEEE C37.47
- Complies with ANSI Z535.4
- Complies With IEEE Std 693-2018
- Complies with 10 CFR Part 431
- Complies with ASTM D3487
- Complies with ASTM D6871
- Complies with NEMA 260-1996
- Complies with CSA C50
- Complies with CSA C2.1-06
- Complies with CSA C227.5
- Complies with CSA C802.1
- Complies with CSA C88
- Complies with CSA C88.1
- Complies with CSA C88-16
- Complies with CSA C227.4
- Complies with CSA C802-3
Product Specification Table
| Rated Capacity (kVA) |
High Voltage (KV) |
Low Voltage (V) |
Connection Symbol |
Short Circuit Impedance (%) |
No-load loss (W) |
On-load loss (W) |
Dimension W*H*D(mm) |
Weight (kg) |
| 800 |
4.16KV 12.47KV 13.2KV 13.8KV 24.94KV 34.5KV or others |
208/120V 480/277V 600V 12470V 13200V 13800V or others |
Dyn1 Ynyn0 Dyn11 Dd0 Ynd11 or others |
2.7 3.1 4.35 5.75 6.0 |
980 |
9350 |
1060*1500*1780 |
2050 |
| 1000 |
|
|
|
|
1160 |
11500 |
1085*1570*1800 |
2450 |
| 1250 |
|
|
|
|
1380 |
13900 |
1160*1610*1890 |
2900 |
| 1600 |
|
|
|
|
1660 |
16600 |
1190*1630*1950 |
3400 |
| 2000 |
|
|
|
|
2030 |
18300 |
1260*1700*2090 |
4100 |
| 2500 |
|
|
|
|
2450 |
19600 |
1150*2150*2250 |
4750 |
| 3000 |
|
|
|
|
3240 |
26500 |
1900*2600*2150 |
6500 |
| 5000 |
|
|
|
|
4500 |
27000 |
2500*2210*3180 |
9500 |
| 7500 |
|
|
|
|
7200 |
32000 |
3660*3100*5100 |
13600 |
| 10000 |
|
|
|
|
8500 |
35500 |
3830*2640*2216 |
15800 |
Production Process