1500kVA Three Phase Pad Mounted Transformer Oil Immersed Step Down 34500v To 208v 120v Dead Front Pad Mount Transformer
WINLEY's 1500kVA three-phase pad mounted transformer is a high-performance power distribution equipment designed for efficient and reliable electricity transmission.
Adopting a loop feed structure, it is suitable for both indoor and outdoor installation scenarios, meeting the power supply needs of various industrial, commercial and residential areas.
Its versatile multi-voltage adaptation, strict compliance with ANSI international standards, authoritative UL/cUL certification, and dedicated grounding porcelain bushing for enhanced safety--all of which together make it a top choice for modern power distribution systems that demand safety, compatibility, and reliability.
Main Technical Specifications
| No. |
Particulars |
Unit |
Specification |
| 1 |
Type |
~ |
pad mounted, loop feed |
| 2 |
Rated capacity |
kVA |
1500 |
| 3 |
No. of Phase |
~ |
3 |
| 4 |
Primary voltage |
V |
34500 |
| 4 |
Primary bushing |
~ |
(6) 35KV class 200A Copper 1-piece bushing + (1) H0 Porcelain bushing |
| 4 |
BIL |
kV |
150 |
| 5 |
Secondary voltage |
V |
208Y/120 |
| 5 |
Secondary bushing |
~ |
(4) 10-hole spade |
| 5 |
BIL |
kV |
30 |
| 6 |
Tapping type |
~ |
off-circuit |
| 7 |
Tapping range |
V |
36200, 35360, 34500, 33640, 33000, 32175, 31350 |
| 8 |
Cooling method |
~ |
ONAN |
| 9 |
Rated frequency |
Hz |
60 |
| 10 |
Vector group |
~ |
Dyn1 |
| 11 |
Insulation class |
~ |
A |
| 12 |
Temperature rise |
℃ |
65/60 (winding/top oil) |
Technical Drawings
Standard Configuration
- The transformer is equipped with a comprehensive set of accessories to ensure safe and stable operation, including:
- 2-position break switch
- Drain with sample valve in HV (High Voltage) side
- Temperature gauge
- Liquid level gauge
- Pressure vacuum gauge
- Pressure relief valve
- Bayonet fuse & current limiting fuse on HV side
- 36KV under oil arrester with ISO switch
- Dedicated grounding terminal matching the H0 grounding porcelain bushing: Ensures tight connection with the bushing, reduces contact resistance, and guarantees continuous and reliable grounding performance.
Key Product Features
One of the most significant advantages of this transformer is its 7-level off-circuit tapping range (36200V, 35360V, 34500V, 33640V, 33000V, 32175V, 31350V). This wide voltage range allows the equipment to seamlessly adapt to different grid voltage fluctuations and diverse application scenarios--whether it is for industrial parks with high-voltage demands, commercial centers requiring stable medium-voltage supply, or residential areas with standard low-voltage needs. The off-circuit tapping design ensures safe and convenient voltage adjustment without interrupting the overall power supply, greatly improving the flexibility and applicability of the transformer in complex power grid environments.
Enhanced Safety via Grounding Porcelain Bushing
- The dedicated H0 grounding porcelain bushing is a key safety feature, with multi-layer protection:
- Superior Insulation: High-purity ceramic, ≥1000MΩ resistance (25℃), isolates terminals to avoid short-circuits.
- Strong Adaptability: Anti-pollution coating, resists harsh elements, stable at -40℃~85℃/≥95% humidity.
- Reliable Connection: Precision inner hole matches copper terminals, ≤0.01Ω resistance, quick fault current discharge.
- Long Lifespan: Ceramic (wear/aging-resistant, UL94 V-0), ≥20 years service, cuts maintenance costs.
Detailed Specifications
| Rated Power (KVA) |
High Voltage (KV) |
Low Voltage (V) |
No-load Loss (W) |
On-load Loss (W) |
Height (mm) |
Depth (mm) |
Width (mm) |
Weight (kg) |
Weight (Lbs) |
| 75KVA |
34.5KV 4.160KV 12.47KV 13.2KV 13.8KV 24940GrdY/14400 1247Grdy/7200 4160GrdY/2400 or others |
277V 347V 480V 600V 120/240V 208GrdY/120 415GrdY/240 480GrdY/277 600Y/347 |
180 |
1250 |
1430 |
910 |
1930 |
645 |
1422 |
| 150KVA |
Same as above |
Same as above |
280 |
2200 |
1530 |
980 |
1510 |
989 |
2180 |
| 300KVA |
Same as above |
Same as above |
480 |
3650 |
1680 |
1080 |
1660 |
1415 |
3119 |
| 500KVA |
Same as above |
Same as above |
680 |
5100 |
1790 |
1160 |
1810 |
1905 |
4200 |
| 750KVA |
Same as above |
Same as above |
980 |
7500 |
2030 |
1300 |
2030 |
2755 |
6074 |
| 1000KVA |
Same as above |
Same as above |
1150 |
10300 |
1854 |
1549 |
1651 |
3235 |
7132 |
| 1500KVA |
Same as above |
Same as above |
1640 |
14500 |
2150 |
1570 |
2210 |
5835 |
12864 |
| 2000KVA |
Same as above |
Same as above |
2160 |
20645 |
2220 |
1600 |
2380 |
6430 |
14175 |
| 2500KVA |
Same as above |
Same as above |
2680 |
23786 |
2330 |
1650 |
3070 |
8865 |
19544 |
| 3000KVA |
Same as above |
Same as above |
3300 |
30300 |
2460 |
1850 |
3260 |
11300 |
24912 |
| 3735KVA |
Same as above |
Same as above |
4125 |
37875 |
2680 |
2060 |
4080 |
14400 |
31746 |
Production Process